Page Manual PC6D CANopen
32
Mode 1 Characteristic (FIR-Filter)
FL
Settling time
to 0.1%
(ms)
3 dB Cut-off
(Hz)
20 dB
damping at
frequency
(Hz)
40 dB
damping at
frequency
(Hz)
Damping in
the
stopband
(dB)
Stopband
(Hz)
Output rate
max.
(samples/s)
0 no filtering
**
1200
1 47 19.7 48 64 >90 >80 1200
2 93 9.8 24 32 >90 >40 600
3 140 6.5 16 21 >90 >26 400
4 187 4.9 12 16 >90 >20 300
5 233 3.9 10 13 >90 >16 240
6 280 3.2 8 11 >90 >13 200
7 327 2.8 7 9 >90 >11 172
8 373 2.5 6 8 >90 >10 150
** Antialiasing filter 17 Hz @ 60 dB/decade
Attention: In mode 1 the output rate is dependant on the selected filter level (FL) and will be
automatically adjusted by the PC6D.
UR Set the update rate (average building) [ 2100sub11 ]
This command will define over how many measurements, from the preceeding IIR or FIR
filter, an average will be calculated. The average will be calculated over 2
UR
samples.
Permitted values 0...7 (see table below).
UR 0 1 2 3 4 5 6 7
No. of samples 1 2 4 8 16 32 64 128
Check / adjustment update rate:
Master (PC / PLC) sends Device responds Result
UR U+0001
Request: average over 2 samples
UR_4 OK
Setting: average over 16 samples
Factory default: 0 [no average, = 1200 samples/s]
Remark to Mode 1
Dependency Output Rate - averaging UR - Filter FL
UR Output Rate samples/s
FL0
FL1
19.7 Hz
FL2
9.8 Hz
FL3
6.5 Hz
FL4
4.9 Hz
FL5
3.9 Hz
FL6
3.2 Hz
FL7
2.8 Hz
FL8
2.5 Hz
0 1200 1200 600 400 300 240 200 172 150
1 600 600 300 200 150 120 100 85.7 75
2 300 300 150 100 75 60 50 43 37.5
3 150 150 75 50 37.5 30 25 21.4 18.7
4 75 75 37.5 25 18.7 15 12.5 10.7 9.4
5 37.5 37.5 18.7 12.5 9.4 7.5 6.26 5.36 4.68
6 18.7 18.7 9.4 6.26 4.68 3.76 3.12 2.68 2.34
7 9.4 9.4 4.68 3.12 2.34 1.88 1.56 1.34 1.18